Measuring techniques for point level detection
In point level detection, a point level switch detects when a certain predefined level is reached. Such a device is employed when it is not necessary to measure every possible intermediate level, as is the case with continuous level measurement. A switching command starts or stops filling equipment such as conveyors or pumps. Point level switches outputting a binary signal can be integrated into a process control system.
Point level detection systems can be used in liquids, pastes, powders or coarse bulk solids.
Typical applications for point level detection are process tanks, storage tanks, silos and pipelines in the process industry. Point level detection is used for minimum or maximum detection, leak detection or overfill protection.
Every industry places its own specific requirements on the measurement technology it uses. A point level switch perfectly adapted to the measuring point can be supplied by taking the properties of the medium as well as the individual process conditions into account.
With the "finder" you can simply and quickly determine the right point level switch for your application.
Choose between the different measuring principles for point level detection of liquids.
» VEGASWING 51
Process fitting thread from G¾, ¾ NPT hygienic fittings
Process temperature -40 … +150 °C
Process pressure -1 … +64 bar (-100 … +6400 kPa)
| |
» VEGASWING 61
Materials 316L, Hastelloy, ECTFE, PFA, enamel
Process fitting thread from G¾, ¾ NPT flanges from DN 25, 1" hygienic fittings
Process temperature -50 … +250 °C
Process pressure -1 … +64 bar (-100 … +6400 kPa)
SIL qualification optionally up to SIL2
| |
» VEGASWING 63
Version tube extension up to 6 m
Materials 316L, ECTFE, PFA Hastelloy, enamel
Process fitting thread from G¾, ¾ NPT flanges from DN 25, 1" hygienic fittings
Process temperature -50 … +250 °C
Process pressure -1 … +64 bar (-100 … +6400 kPa)
SIL qualification optionally up to SIL2
| |
» VEGASWING 66
Material 316L, Inconel 718, Hastelloy
Process fitting thread from G1, 1 NPT flanges from DN 40, 2"
Process temperature -196 … +450 °C
Process pressure -1 … +160 bar (-100 … +16.000 kPa)
SIL qualification up to SIL2 (homogeneous redundancy up to SIL3)
| |
|
» VEGACAP 62
Version partly insulated rod
Process fitting thead from G¾, ¾ NPT flanges from DN 50, 2"
Materials steel, 316L, PTFE
Process temperature -50 … +200 °C
Process pressure -1 … +64 bar (-100 … +6400 kPa)
| |
» VEGACAP 63
Version fully insulated rod
Process fitting thread from G¾, ¾ NPT flanges from DN 50, 2"
Process temperature -50 … +200 °C
Process pressure -1 … +64 bar (-100 … +6400 kPa)
| |
» VEGACAP 64
Version fully insulated rod
Process fitting thread from G¾, ¾ NPT flanges from DN 50, 2"
Process temperature -50 … +200 °C
Process pressure -1 … +64 bar (-100 … +6400 kPa)
| |
» VEGACAP 65
Version partly insulated cable
Measuring range up to 32 m
Process fitting thread from G1, 1 NPT flanges from DN 50, 2"
Process temperature -50 … +200 °C
Process pressure -1 … +64 bar (-100 … +6400 kPa)
| |
» VEGACAP 66
Version fully insulated cable
Measuring range up to 32 m
Process fitting thread from G1, 1 NPT flanges from DN 50, 2"
Process temperature -50 … +150 °C
Process pressure -1 … +40 bar (-100 … +4000 kPa)
| |
» VEGACAP 69
Process fitting flanges from DN 50, 2"
Process temperature -50 … +100 °C
Process pressure -1 … +2 bar (-100 … +200 kPa)
SIL qualification optionally up to SIL2
| |
|
» VEGAMIP T61
Measuring range up to 100 m
Process fitting thread G1½, 1½ NPT flanges Clamp
Process temperature -40 … +80 °C +450 °C with mounting adapter
Process pressure -1 … +4 bar (-100 … +400 kPa)
| |
» VEGAMIP R61
Measuring range up to 100 m
Process fitting thread G1½, 1½ NPT flanges Clamp
Process temperature -40 … +80 °C +450 °C with mounting adapter
Process pressure -1 … +4 bar (-100 … +400 kPa)
| |
|
» EL 1
Version fully insulated rod
Process temperature -50 … +130 °C
Process pressure -1 … +63 bar (-100 … +6300 kPa)
| |
» EL 3
Version partly insulated rod
Process fitting thread G1½
Process temperature -50 … +130 °C
Process pressure -1 … +63 bar (-100 … +6300 kPa)
| |
» EL 4
Version partly insulated rod
Process fitting thread G1½
Process temperature -20 … +100 °C
Process pressure -1 … +6 bar (-100 … +600 kPa)
| |
» EL 6
Version partly insulated cable
Process fitting thread G1½
Process temperature -20 … +100 °C
Process pressure -1 … +6 bar (-100 … +600 kPa)
| |
» EL 8
Version partly insulated rod
Process temperature -10 … +60 °C
Process pressure -1 … +6 bar (-100 … +600 kPa)
| |
» VEGAKON 61
Version partly insulated compact level switch
Process fitting thread G1, 1 NPT cone DN 25
Process temperature -40 … +150 °C
Process pressure -1 … +25 bar (-100 … +2500 kPa)
| |
» VEGAKON 66
Version compact level switch
Process fitting thread G1½
Process temperature -40 … +100 °C
Process pressure -1 … +6 bar (-100 … +600 kPa)
| |
|
» MINITRAC 31
Applications density and level detection measurement
Version sensor with integrated NaI detector
Process fitting from outside on the vessel or pipeline
| |
|